APPENDIX B: KISTLER-MORSE
®
PROTOCOL SERIAL COMMANDS
‘P9’ Command — Write Setpoint High/Low Mode
This command is sent by the master to set the setpoint high/low mode of an STXplus.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where 0
is low mode or 1 is high mode. For this example, the master sets setpoint 2’s high/low mode for
an STXplus at address 01 to 1 (high mode). Any of the 6 leading zeros may be omitted.
Request from Master Response from STXplus
>aaP9n000000dssr Ar Format
>01P9214Dr Ar Example
‘G7’ Command — Read Setpoint Tracking Mode
This command is sent by the master to request the STXplus to send the setpoint tracking mode.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where 0
is setpoint tracks gross weight or 1 is setpoint tracks net weight. The default value is 0 (tracking
gross). For this example, the master requests setpoint 2’s tracking mode for an STXplus at
address 01 which returns 0 (tracking gross) and a checksum of 50.
Request from Master Response from STXplus
>aaG7nssr A000000dssr Format
>01G7211r A000000050r Example
‘P7’ Command — Write Setpoint Tracking Mode
This command is sent by the master to set the setpoint tracking mode of an STXplus. Acceptable
values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where for 0 the
current output tracks gross weight or for 1 the current output tracks net weight. For this example,
the master sets setpoint 1’s tracking mode for an STXplus at address 01 to 1(tracking net). Any of
the 6 leading zeros may be omitted.
Request from Master Response from STXplus
>aaP7n000000dssr Ar Format
>01P7114Ar Ar Example
‘Rg’ Command — Read Setpoint State
This command is sent by the master to request the STXplus to send the setpoint state.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where
0 is setpoint off or 1 is setpoint on. The default value is 0 (setpoint off). For this example, the
master requests setpoint 2’s state for an STXplus at address 01 which returns 0 (setpoint off) and
a checksum of 50.
Request from Master Response from STXplus
>aaRgnssr A000000dssr Format
>01Rg24Cr A000000050r Example
B-25