Kistler-morse KM STXPlus Manuel d'utilisateur Page 49

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 76
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 48
APPENDIX B: KISTLER-MORSE
®
PROTOCOL SERIAL COMMANDS
Request from Master Response from STXplus
>aaL4000000dssr Ar Format
>01L4112r Ar Example
‘K5’ Command — Read AB-RIO Rack Size
This command is sent by the master to request the STXplus to send the AB-RIO rack size. The
range of acceptable values is 0-3 where 0 for 1/4, 1 for 1/2, 2 for 3/4, or 3 for full. For this
example, the master requests AB-RIO rack size for an STXplus at address 01 which returns 0
(1/4) and a checksum of 50.
Request from Master Response from STXplus
>aaK5ssr A000000dssr Format
>01K5E1r A000000050r Example
‘L5’ Command — Write AB-RIO Rack Size
This command is sent by the master to set the AB-RIO rack size of an STXplus. The range of
acceptable values is 0-3 where 0 for 1/4, 1 for 1/2, 2 for 3/4, or 3 for full. For this example, the
master sets AB-RIO rack size for an STXplus at address 01 to 1 (1/2). Any of the 6 leading zeros
may be omitted.
Request from Master Response from STXplus
>aaL5000000dssr Ar Format
>01L5113r Ar Example
‘K6’ Command — Read AB-RIO Last Rack
This command is sent by the master to request the STXplus to send the AB-RIO last rack. The
range of acceptable values is 0-1 where 0 is Yes or 1 is No. For this example, the master requests
AB-RIO last rack for an STXplus at address 01 which returns 0 (No) and a checksum of 50.
Request from Master Response from STXplus
>aaK6ssr A000000dssr Format
>01K6E2r A000000050r Example
‘L6’ Command — Write AB-RIO last rack
This command is sent by the master to set the AB-RIO last rack of an STXplus. The range of
acceptable values is 0-1 where 0 is Yes or 1 is No. For this example, the master sets AB-RIO last
rack for an STXplus at address 01 to 1 (Yes). Any of the 6 leading zeros may be omitted.
Request from Master Response from STXplus
>aaL6000000dssr Ar Format
>01L6114r Ar Example
‘K7’ Command — Read AB-RIO Mode
This command is sent by the master to request the STXplus to send the AB-RIO mode. The
range of acceptable values is 0-1 where 0 is Discrete or 1 is Block. For this example, the master
requests AB-RIO mode for an STXplus at address 01 which returns 0 (Discrete) and a checksum
of 50.
B-30
Vue de la page 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 75 76

Commentaires sur ces manuels